Laserfiche WebLink
�p <br /> Line Leak Detector Test Data Sheet <br /> Station# 2186 Date 3/6 2009 <br /> Address 3212 N California <br /> Stockton, Ca <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer RJ RJ <br /> Model CPT CPT <br /> Full Operating Pressure (psi) 3 3 sl 31 psi <br /> Line Bleed Back(ml) 200ml 175ml <br /> Trip Time (sec) 154 sec 242 sec <br /> Metering Pressure (psi) <br /> F/E Holding Pressure (psi) 15 psi 24 psi <br /> Test Leak Rate (mllmin)(gph) 189 ml 187 ml <br /> PASS or FAIL Pass Pass <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor_Gettler-Ryan Inc. <br /> Technician Chris San Nicolas Lic# 220793 <br /> Signature <br />