Laserfiche WebLink
Facility Name: Arco #2186 (Page 2) <br /> D. Results of Testing/Servicing <br /> Complete the following checklist: <br /> Software Version Installed: 329.00 <br /> Yes ❑No* Is the audible alarm operational? <br /> •Yes El No* Is the visual alarm operational? <br /> ®Yes ❑No* Is the print function operational? <br /> ®Yes F1 No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ®Yes ❑No* Were all sensors installed at lowest point of secondary containment and positioned so that other <br /> e ui ment will not interfere with their proper operation? <br /> Yes El No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. <br /> ❑ N/A modem)operational? <br /> ®Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary <br /> ❑N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If <br /> yes: which sensors initiate positive shutdown? (Check all that apply) ® Sump Sensors; <br /> Dispenser Containment Sensors. <br /> Did you confirm positive shutdown due to leaks and sensor failure/disconnection? ®Yes; ❑ No. <br /> ® No* For tank systems that utilize the monitoring system as the primary tank overfill warning device, is <br /> ❑ N/A the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? At <br /> Yes what percent of tank capacity does the alarm trigger? 90% <br /> El Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other <br /> equipment replaced and list the manufacturer name and model for all replacement parts in Section <br /> E, below. <br /> ❑Yes* ®No Was liquid found inside any secondary containment systems designed as dry systems? (Check all <br /> that apply)❑ Product; ❑Water. If yes,describe causes in Section E, below. <br /> ®Yes ❑No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if <br /> applicable <br /> ®Yes ❑No* Is all monitoring equipment oerational per manufacturer's specifications? <br /> E. Comments: <br />