Laserfiche WebLink
.18!k low <br /> 4 LINE LEAK DETECTOR TEST <br /> Facility#: 2186 Date: 02/14/12 <br /> Address: 3212 N. California St. <br /> City, State: Stockton, Ca <br /> Testing Information <br /> 1 2 3 4 5 <br /> Product: 87 91 <br /> Manufacturer Veeder-Root Veeder-Root <br /> Leak Detector Serial Number 262201 H38041 <br /> Leak Detector Model No. 848480 848480 <br /> Full Operating Pressure (psi): 32 32 <br /> Test Leak Rate(ml/min)(gph) 3.00 3.00 <br /> Bleed Back Rate(ml): <br /> Turbine Holding Pressure(psi): 0 0 <br /> Metering Pressure (psi): N/A N/A <br /> Open/Trip Time(mechanical only): N/A N/A <br /> Pass/Fail Pass Pass <br /> Comments: <br /> Note: Pass= Leak detector reads leak and meters line. <br /> Fail = Leak detector did not read leak. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment <br /> manufacturers procedures and limitations and the results as listed are to my knowledge true and correct.The mechanical leak test detector <br /> test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor FASTECH-Fueling&Services Technologies, Inc. <br /> Technician: Isaac Anderson AI ch eetro Inc. Lic#: 623541 A-Haz <br /> Signature: <br />