Laserfiche WebLink
RECEIVED <br /> 43 <br /> JAN 3 1 2017 <br /> Line Leak Detector Test Data Sheet <br /> ENVIRONMENTAL HEALTH <br /> Station # Arco SS 2186 Date 1�5 20 17 DEPARTMENT <br /> Address 3212 N. California, Stockton, CA <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure (psi) 29 32 <br /> Line Bleed Back(ml) NA NA <br /> Trip Time(sec) NA NA <br /> Metering Pressure (psi) NA NA <br /> F/E Holding Pressure (psi) 21 21 <br /> Test Leak Rate(ml/min)(gph) 189m1 189m1 <br /> PASS or FAIL P P <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Tim Adams Lic# <br /> Signature <br />