Laserfiche WebLink
20 � - <br /> HOW TO LOCATE THE POSITION OF THE <br /> 71SO AT 95%TANK CAPACITY Measuring Stick <br /> The length of the upper tube and the placement of l <br /> the 71 SO valve body determine the shut-off point. _ <br /> Following the standard instructions for the OPW <br /> 71 SO will provide for initial shutoff at 95%. In all <br /> cases, the upper tube length must be a minimum of <br /> 6-1/2"plus the length of the riser pipe. All length f <br /> measurements are in inches. Riser Pipe <br /> INSTRUCTIONS with Face {A) <br /> Seal Ada or <br /> To Tank (B) <br /> 1.) Find tank capacity(in gallons)from tank Y Top(I.D.) To Tank <br /> calibration chart provided by tank manufacturer. Bottom <br /> 2.) Calculate 95%of capacity. g 9153. <br /> 6-1/2" <br /> 3.) Locate the 95% volume number on the tank <br /> calibration chart. <br /> 4.) Find the dipstick number(X)which corresponds Figure 1 <br /> to the 95%tank volume. And, find the dipstick <br /> number(Y)which corresponds to the 4 EXAMPLE <br /> 100%volume. 1,97_//, �� 1.) For an Owens-Coming Model G-3 Fiberglass® <br /> �f Tank Calibration Chart: <br /> 5.) Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gal., nominal 9,403 gal. <br /> diameter(Y)to find the upper tube reference NOTE: Use actual capacity only <br /> number(Z). <br /> (y)- (X) =(Z)7 ,ice /Z�� �� 2.) 95% of actual tank capacity=0.95 x <br /> l 9403 gal.= 8933 gal. <br /> 6.) Subtract 2"ficim ( )to find the upper tube epth <br /> (C)• 3.)The closest number which is less than 8933 gal. <br /> (Z) -2"= C /4—Y Is 8910 gal. Choosing the closest number less <br /> than 95%of actual capacity ensures that the <br /> 7.) Is C less than 6-112"? N D initial shutoff will occur when the tank is no more <br /> than 95%full. <br /> NO Upper tube length is C plus t distance <br /> from the top of the Face Se Adaptor 4.)The calibration chart reading of 8910 gal. <br /> installed on the riser pipe t the inside, top corresponds to a dipstick measurement of 82". <br /> lip of the storage (A). <br /> Upper Tube Length— + A 5•) Dipstick number(X)= 82" <br /> U <br /> PP g — ( ) Tank diameter(Y)= 92" <br /> (Y)-(X) =(Z) (92"-82" = 10") <br /> YES Upper tube length i 6-1/2"plus the riser (Z)= 10" <br /> pipe measureme (A). <br /> Upper Tube L 7.) (Z)-2"= C (10"-2"=8") <br /> PR gth =6-112"+ (A) C = 8" <br /> NOTE: You st find the actual tank capacity 7.) Is 8" less than 6-1/2"? <br /> number that correlates to the 6-1/2"+(A)depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system. riser pipe to the inside, top lip of the storage <br /> tank and obtain measurement(A). <br /> Registered T.M.-Owens Coming Fiberglass Corporation Upper tube length =C + (A) <br /> 64 <br />