Laserfiche WebLink
Closed <br /> Figure 29 <br /> INSP 6 . If there is no apparent damage or restrictions <br /> reinstall the valve per the above instructions and test <br /> per local requirements . <br /> 71 SO Performance Specifications <br /> This Overfill Prevention Valve has been manufactured <br /> and tested to, and met, the following California specifi- <br /> cations . Performance Requirement : Leak rate to be less <br /> than or equal to 0. 17 CFH@2 .0" W. C . <br /> Torque Specification <br /> Taptite Screws, # 10 - 24 thread cutting , 20 in - lbs mini - <br /> mum to 35 indbs maximum . Testable Models Only. <br /> Socket Adaptor, 1 /4" NPT, 3 . 5 ft- lbs (42 in - lbs) minimum <br /> to 5 .0 ft- lbs (60 in - lbs) maximum . <br /> IMPORTANT: Leave these installation instructions <br /> and maintenance procedures with the station opera - <br /> tor . <br /> 19 <br />