Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Page 1 of 1) <br /> Type of Action ❑Installation Inspection ❑Repair Inspection ❑x 36 Month Inspection <br /> I. FACILITY INFORMATION <br /> CERS ID 10181387 Date of Overfill Prevention Equipment Inspection <br /> 1/15/2019 <br /> Business Name(Same as Facility Name or DBA-Doing Business As) <br /> Ryder Truck Rental <br /> Business Site Address City ZIP Code <br /> 3633 Duck Creek Dr. Stockton 95215 <br /> II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection(Print as shown on the ICC Certification.) Phone# <br /> Robert Henninger 1 (408) 942-8686 <br /> Contractor/Tank Tester License# ICC Certification# ICC Certification Expiration Date <br /> 396575 5252265-UT 7/13/2019 <br /> Overfill Prevention Equipment Inspection Training and Certifications(List applicable certifications.) <br /> Veeder-Root-A25027 04/15/19 <br /> III. OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION <br /> Inspection Method ❑Manufacturer Guidelines(Specify): <br /> Used: <br /> ❑x Industry Code or Engineering Standard(Specify): RP-1200 <br /> ❑Engineered Method(Specify): <br /> Attach the inspection procedures and all documentation required to determine the results. #of Attached Pages <br /> TANK ID:(By tank number,stored product, etc.) T1: Diesel T2: Diesel T3: Motor Oil T4: Used Oil <br /> What is the tank inside diameter?(Inches) 96" 96" 96" 64" <br /> Is the fill piping secondarily contained? 0 Yes ❑No I]Yes ❑No [E Yes ❑No 0 Yes ❑No <br /> Is the vent piping secondarily contained? [E]Yes 0 No 2 Yes ❑No 9 Yes ❑No ER Yes ❑No <br /> Overfill Prevention Equipment Manufacturer(s) Veeder-Root Veeder-Root Veeder-Root Veeder-Root <br /> What is the overfill prevention equipment response ❑Shuts Off Flow ❑Shuts Off Flow ❑Shuts Off Flow ❑Shuts Off Flow <br /> when activated? <br /> (Check all that apply.) ❑Restricts Flow ❑Restricts Flow ❑Restricts Flow ❑Restricts Flow <br /> ❑Q AN Alarm ❑x AN Alarm ❑x AN Alarm ❑x AN Alarm <br /> Are flow restrictors installed on vent piping? ❑Yes 0 No ❑Yes ❑x No ❑Yes ❑x No ❑Yes ❑x No <br /> At what level in the tank is the overfill prevention set <br /> to activate?(Inches from bottom of tank.) 80.5" 80.5" 80.5" 53.5" <br /> What is the percent capacity of the tank at which the <br /> overfill prevention equipment activates? 90% 90% 90% 90% <br /> Is the overfill prevention in proper operating condition ❑x Yes ❑x Yes ❑Q Yes ❑X Yes <br /> to respond when the substance reaches the <br /> appropriate level? ❑No(Specify in V.) ❑No(Specify in V.) ❑No(Specify in V.) ❑No(Specify in V.) <br /> IV. SUMMARY OF INSPECTION RESULTS <br /> Overfill Prevention Inspection Results E Pass ❑Fail I Z Pass ❑Fail I ❑x Pass ❑Fail I]Pass ❑ Fail <br /> V. COMMENTS <br /> Any items marked"Fail'must be explained in this section. Any additional comments may also be provided here. <br /> VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPECTION <br /> I hereby certify that the overfill prevention equipment was inspected in accordance with California Code of Regulations,Title 23, <br /> Division 3,Chapter 16,Section 2637.2 and all <br /> the information contained herein is accurate. <br /> UST Service Technician Signature <br /> If the facility has more components than this form accommodates,additional copies of this page may be attached. <br /> CERS=California Environmental Reporting System,ID=Identification,UST=Underground Storage Tank,ICC=International Code Council,AN=Audible and Visual <br /> UN-109 www.unidocs.org 111 -Rev.06/14/18 <br />