Laserfiche WebLink
X` l <br /> RECISION <br /> INDUST-RIES <br /> MARCH 4 , 1387 <br /> INC - <br /> ENV1F,,,)4rLtiTAL HEALT <br /> G E N E R A L SAFEWAY MEAT PLANT F Ekfvl I I /SERVICES <br /> ENGINEERING P O BOX 8347 <br /> CONTRACTORS STOCKTON , CA 95208 <br /> & S E R V I C E <br /> S T A T 1 0 N ATTENTION JULIAN MUNOZ <br /> MAINTENANCE # <br /> LICENSE NO 467293 LOCATION SAFEWAY MEAT PLANT I <br /> 1111 Navy Drive , Stockton , CA 95206 <br /> RESULTS OF TANK TESTS PERFORMED JANUARY 19 , 1987 <br /> TANK # 1 12 , 000 gallon diesel fuel tank <br /> Full system test indicated a volume chance <br /> of - 021 gallons per hour under test <br /> conditions II <br /> Full system test v. ithin state gul (1011 np <br /> TANK #2 - 12 , 000 gallon dLe-el fuel tank - <br /> Full system test indicated a volume ClIange <br /> Of - 019 gallons per hour under test <br /> conditions <br /> Full System test within state quido lines <br /> TANK #4 - 12 , 000 gallon diesel fuel tank - <br /> Full system test Indicated ., volume chatlae <br /> of - 031 gallons per hour under test <br /> conditions <br /> Full system test within state quzdellnrs <br /> TANK # 3 - was untestable due to a laraP ] nss of fuel <br /> I <br /> prior to testing Overnight the fuel 1c-.Vel <br /> in the tank dropped approximately f, inches <br /> Further excavation is needed to discover the <br /> possible cause <br /> PRECISION INDUSTRIES , INC <br /> WARREN DEE FOWLES <br /> FIELD SUPERINTENDENT <br /> WDF/psw <br /> 2191 NAVY DR STOCKTON CALIFORNIA 95206 209/462 9r,II <br />