Laserfiche WebLink
t <br />PUBLIC HEALTH SERACES <br />SAN JOAQUIN COUNTY <br />ENVIRONMENTAL HEALTH DIVISION <br />Ernest M. Fujimoto, M.D., M.P.H., Acting Health Officer <br />445 N. San Joaquin Street • P.O. Box 388 0 Stockton, CA 95201-0388 <br />(209) 468-3420 <br />MEMORANDUM <br />Date March 13, 1995 <br />From Michael Kith, Sr REHS <br />San Joaquin County <br />Environmental Health Division <br />To Mike Flores <br />Stockton Service Station & Equipments <br />Re : Installation plan for Flag City Chevron, 6421 Paddock PI, Lodi. <br />Upon reviewing the installation plan for the above facility, the following deficiencies were <br />observed : <br />1. Specify what pump (tank) sump will be used. <br />2. Submit information on UL listed status for the proposed Eviron dispenser <br />sump for gasoline and alcohol compatibility. <br />3. Provide the location for the monitoring panel. <br />4. Specify in writing what kind of probes will used and their locations. <br />5. Environ Geoflex hose is approved for primary piping only. Specify the <br />secondary piping. Submit cross sectional diagram. <br />6. Calculation for tank anchoring and hold-down must be certified by a <br />licensed engineer unless it comes from the manufacture. <br />7. Is the pump shut off completely when the alarm is activated, leak is <br />detected or the monitoring system is disconnected. If so, submit <br />explanation and diagram. <br />8. In future plan submitted to PHS-EHD must contained all information <br />specified on PHS-EHD UST installation guideline. <br />A Division of San Joaquin County Health Care Services <br />