4162 ad Street <br /> mhftm t OCT 2 2 2018 Galt, CA 95632 <br /> (209) 744-0113 Fax (209) 744-0116 <br /> ENVIRONMENTAL HEALT <br /> DEP . .fR 4 <br /> Veeder-Root In-Station Diagnostics Balance Vapor Flow Meter Operability Test Procedure <br /> Permit Number: N-714 Date of Test: 9/26/2018 Time: <br /> Site Name: FLAG CITY CHEVRON <br /> Site Address: 6421 CAPITOL AVENUE <br /> City: LODI, CA Zip: 95240 Technician: ZANE NIMMO <br /> VST: 3000839502 <br /> District: 9/26/2018 Veeder-Root: A28446 <br /> Calibration Date: 3/10/2019 <br /> Flow ISD Flow Meter Gas Flow Meter <br /> Meter Fueling Converted %Diff. Pass/ <br /> Serial No. Point Start Stop Diff. (in gal) Start Stop Diff.(in cf) Diff. in al) Fail <br /> 5 6 520 1 /2 1.786 9.334 7.548 7.984 1.067 -5.46 Pass <br /> 5 6 5 19 3/4 52.344 59.538 7.194 7.685 1.027 -6.38 Pass <br /> 5 6 525 5/6 37.673 45.753 8.080 1 7.921 1.059 2.00 Pass <br /> 5 6 1 3 5 7/8 38.945 46.423 7.478 7.782 1.040 -3.91 Pass <br /> 3 1 2 43 9/10 68.255 76.867 8.612 8.436 1.128 2.08 Pass <br /> 63 1 4 8 11 / 12 1 79.415 87.423 8.008 7.963 1.064 0.56 Pass <br /> a <br /> ISD_Differencesi11 Gas_Flow_Meter_Dii erencegall°�. <br /> Gallons=Cubic-Feet x 7.481 /oD fference= X100 <br /> Gas-Flow-Meter-Differenceg'U.,. <br /> I declare, under penalty ofperjury under the laws of the state of California that based on information and beliefformed after reasonable inquiry, the <br /> statements and information provided in this document are true, accurate, and complete. <br /> Signature of Technician: Date: 9/26/2018 <br />