Tracy Mazda Waste Anti-. _aeze Tank and Waste Oil Assessment <br /> Written Assessment per CCR Title 22 <br /> Tank Assessment Page Tank Name: Waste Oil <br /> Tankage: 4 years <br /> Remaining service life: Twenty years, <br /> Re-inspect in 5 years <br /> Tank Construction: <br /> Shape: Rectangular <br /> Orientation: Horizontal <br /> Location (above/below ground): Above Ground <br /> Material of construction: Steel <br /> Thickness and method used to determine: 0.19" UTG <br /> Lining material & thickness (if applicable): NA <br /> Corrosion Protection equipment: contents compatible with steel. <br /> Structural support: Anchored to concrete floor <br /> Other identifying features.- <br /> Piping <br /> eatures:Piping and ancillary equipment (pumps): <br /> Piping Material of Construction: Copper <br /> Piping Diameter: 1" <br /> Pump location(s): Garage <br /> Pump types)/capacities: AOD, Husky 1040, 5 gpm <br /> Strandberg Associates 1(866) 388-0404 (650) 329-8918 rwaterguy(a)rwaterguy.com 12 <br />