Laserfiche WebLink
Hazardous Waste Tank System September <br /> Written Assessment per CCR Title 22 p <br /> Tracy Mazda, 2680 Auto Plaza Way, Tracy, CA 95304 2018 <br /> Seismic/Earthquake: Provides tank information, seismic acceleration and <br /> seismic calculations showing evidence that the tank is sufficiently anchored for <br /> the seismic forces that may be anticipated during an earthquake. <br /> Tracy Mazda <br /> Used Antifreeze Tank <br /> T T <br /> 38" . 32" <br /> 1. <br /> 1 <br /> T T <br /> 40" 37" <br /> concrete <br /> Mfg Chem Tainer <br /> Standard- Unknown, single wall Tank requires anchors for sliding <br /> Date of IAfg: 2009 <br /> Tank Wall Thickness: 0.35" � <br /> Weight of Tank and Contents: 1,157 lbs <br /> Material of Construction: Polyethylene <br /> Tank Volume: 139 gallons <br /> Operating Volume: 125 gallons <br /> Overturning kloment Arm: 20" i n <br /> Resisting Moment Arm: 16" �+ u <br /> Sds: 1.03 Anchor 1 2"dia <br /> 4 Places, 3,432 lbs shear <br /> Strandberg Associates 1(866) 388-0404 rwaterauy(aDrwaterguy_y.com 21 <br />