Laserfiche WebLink
Hazardous Waste Tank System <br /> Written Assessment per CCR Title 22 September <br /> Tracy Mazda, 2680 Auto Plaza Way, Tracy, CA 95304 2018 <br /> Seismic/Earthquake: Provides tank information, seismic acceleration and <br /> seismic calculations showing evidence that the tank is sufficiently anchored for <br /> the seismic forces that may be anticipated during an earthquake. <br /> Tracy Mazda <br /> Used Antifreeze Tank <br /> T T <br /> 3L <br /> 1 <br /> 1 <br /> T T <br /> 1 yi <br /> concrete <br /> Mfg Chem Tainer <br /> Standard: Unknown, single wall Tank requires anchors for sliding <br /> Date of Mfg- 2009 <br /> Tank W0 Thickness: 0.35" <br /> Weight of Tank and Contents: 1,157 lbs <br /> Material of Construction: Polyethylene <br /> Tank Volume: 139 gallons <br /> Operating Volume 125 gallons <br /> Overturning Moment Arm: 20" , It <br /> Resisting Moment Arm: 16" �� u <br /> Sds: 1.03 Anchor 1;2"dia <br /> 4 Places, 3.432 lbs shear <br /> Strandberg Associates 1(866) 388-0404 rwaterquy(o)rwaterguy.com 21 <br />