Laserfiche WebLink
0 9 <br />requirements. <br />5. The protected and insulated AST systems shall have a thru-tank leak detector tube to <br />allow for physical checkup and monitoring capability between the primary and the <br />secondary containment. <br />6. The primary steel tank shall be pressurized at 5 psig during concrete encasement. <br />7. The outer surface of the primary steel tank shall be covered by a minimum of 1/4" <br />thick (6.4 mm) Styrofoam insulation panels. <br />8. The secondary containment shall consist of a 30 NEI thick (0.76 mm) High -Density <br />Polyethylene membrane enclosing the steel tank and insulation material. <br />9. The primary steel tank and the secondary containment shall be encased in six inches <br />of monolithic reinforced concrete, with minimum design strength of 4,000 and 5,000 <br />psi at 28 days depending on the tank size. The concrete design shall include the <br />following for long-term durability: air entrainment, water reducing admixture, and <br />steel reinforcement. Concrete encasements with seams will not be approved. <br />10. The protected and insulated AST systems shall be of concrete exterior and a <br />continuous and visually verifiable monolithic (seamless) pour on top, bottom, ends, <br />and sides and contain no cold joints or heat sinks (heat transfer points). The AST <br />must be shop fabricated and tested in accordance with the LJL listings. Designs that <br />use two layers of steel with insulation material between them will not be approved. <br />Aboveground Storage Tanks Specifications <br />Page 3 of 3 <br />08/OM005 <br />11. No steel or insulating material shall come in contact with the concrete or other <br />corrosive material. <br />12. All openings shall be from the top only. <br />13. All exiposed metal with the excevtion of stainless steel must be,,00wder co,*eA • corrosion. <br />14. The protected and insulated AST systems shall include a 7 or 15 -gallon powder <br />coated or stainless steel, UL listed spill containment, and shall include normally <br />closed valve to release spilled product into the primary steel tank. Spill containment <br />which route the spilled product into interstitial area will not be approved. <br />15. The protected and insulated AST systems shall have a coated concrete exterior to <br />resist weather and reflect <br />16. The protected and insulated AST systems shall have a warranty of 30 years for <br />systems 2,000 gallon capacity and larger and 20 years for systems 1,000 gallon <br />capacity and smaller with optional 30 -year warranty. <br />17. The protected and insulated AST systems design shall have been in use for a <br />minimum of ei liteen, )giears. The mam; rer <br />• system failure in 28,000 units produced. <br />18. The protected and insulated AST systems shall have two (2) bolts for connecting <br />grounding conductors for lightning protection in accordance with NFPA 780. <br />