Laserfiche WebLink
S b N J 0 A Q U I N Environmental Health Department <br /> COUNTY— <br /> Aboveground <br /> CUNTYAboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MOUNTAIN VALLEY EXPRESS INC 1 1019 BESSEMER AVE, MANTECA April 11, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 718 CFR 112.8(c)(11) Failed to locate properly or provide sufficient secondary containment for mobile/portable <br /> containers. <br /> -Two blue metal 55 gallon drums of oil and one 90 gallon mobile tank of gear oil were observed with insufficient <br /> secondary containment in the maintenance shop. <br /> -Portions of the SPCC plan state that spill pallets are in use for mobile containers. <br /> -Section 4.2.11 of the SPCC plan states that there are no mobile or portable containers at this facility. <br /> Portable oil storage containers must be positioned or located to prevent a discharge and shall be furnished with a <br /> secondary means of containment sufficient to contain the capacity of the largest single container with sufficient <br /> freeboard to contain precipitation. Immediately provide sufficient secondary containment for this and all other <br /> portable containers at this facility, or provide equivalence as allowed by CFR 112.7(a)(2). The SPCC plan should <br /> accurately address mobile and portable containers. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by May 13, 2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209)468-3420. <br /> Inspector Provided: Return to Compliance certification, flier for free CUPA classes, SP001 monthly and yearly <br /> inspection forms <br /> Tanks Observed: <br /> -10,000 gallon double-wall diesel <br /> -600 gallon single wall oil <br /> -550 gallon double-wall used oil <br /> -90 gallon portable gear oil tank <br /> -Up to four 55 gallon drums of oil <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: April 11, 2019 Inspector: Inspector Phone: <br /> Printed Name and Title: LYDIA BAKER, REHS (209)468-8257 <br /> WUI Dan Souza,Vice President <br /> FA0010328 PR0515715 SCO01 04/11/2019 <br /> EHD 28-01 Rev.09/27/2018 Page 6 of 6 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />