Laserfiche WebLink
TABLE 6 <br /> Inspection and Testing Program <br /> MOUNTAIN VALLEY EXPRESS <br /> 1019 Bessemer Avenue, Manteca, California <br /> Facility <br /> Component Action Frequency/Circumstances <br /> Aboveground Test container integrity. Combine visual Following a regular schedule (monthly, <br /> container inspection with another testing technique annual, and during scheduled inspections) <br /> (non-destructive shell testing with an and whenever material repairs are made, <br /> Ultrasonic Thickness Gauge meter). as deemed necessary by Facility <br /> Inspect outside of container for signs of management. <br /> deterioration and discharges. <br /> Container supports Inspect container's supports and Following a regular schedule (monthly, <br /> and foundation foundations. annual, and during scheduled inspections) <br /> and whenever material repairs are made. <br /> Liquid level sensing Test for proper operation. Monthly <br /> devices overfill <br /> Concrete drainage Inspect for signs of deterioration, Monthly <br /> area discharges, or accumulation of oil inside <br /> concrete containment areas. <br /> Visually inspect content for presence of <br /> oil. Prior to draining <br /> II aboveground Assess general condition of items, such Monthly <br /> valves, piping, and as flange joints, expansion joints, valve <br /> appurtenances glands and bodies, catch pans, pipeline <br /> supports, locking of valves, and metal <br /> surfaces. <br />