Laserfiche WebLink
Hazardous Waste Tank System <br />Written Assessment per CCR Title 22 <br />Stockton CSMS Stockton, CA <br />Foundation Analysis, Waste Oil Tank, Stockton CSMS <br />Soil Type: Clay Sandy, Allowable Pressure, psi <br />10.42 <br />area of foundation, int <br />6400 <br />depth of concrete, in <br />4 <br />weight of concrete, lbs <br />708.74 <br />weight of tank and contents, lbs <br />4377 <br />total weight on soil, lbs <br />5085.74 <br />pressure on soil, psi <br />0.79 <br />Safety Factor <br />13.11 <br />Soil is Okay for Foundation <br />Concrete Analysis <br />fc" psi <br />2500 <br />cpbr <br />0.7 <br />a <br />1 <br />loaded area, in2 <br />192 <br />Foundation Bearing Capacity, Fb, lbs <br />112000 <br />Combined weight of tank and contents, lbs <br />4377 <br />Safety Factor <br />25.59 <br />Foundation is Okay for tank. <br />Integrity testing findings: Based on the ab <br />results obtained from that test, the tank has s <br />use. Initials: <br />noted integrity test and the <br />1pnt integrity for its intended <br />OTIE <br />Strandberg Associates 1(866) 388-0404 (650) 329-8918 rwaterquyarwaterquy.com <br />12 <br />