Laserfiche WebLink
INVOICE #LN000074 TEST DATE: 01/13/96 <br /> AFFORDA-TE$T <br /> PO BOX 36 <br /> THORNTON, CA. 95686 <br /> ( 209 ) 794-0102 or ( 800) 524-9087 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> ELITE IV J AND L EXXON <br /> 2535 WIGWAM DR. 8125 EL DORADO <br /> @ MATTHEWS BLVD. <br /> STOCKTON, CA FRENCH CAMP, CA <br /> 95205 95231 <br /> CONTACT: GIPSON, TIM CONTACT: GIPSON, TIM <br /> PHONE # : ( 209)461-6337 PHONE # : ( 209) 982-0912 <br /> ***** COMMENT LINES ***** <br /> TWO 12K TANKS, ONE SPLIT 6K/6K, SUP/DIE, MANIFOLDED & BALANCED <br /> PRESSURE LINES, LD 2000 LEAK DETECTORS <br /> 8 HOSES. <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS . 05 GALLONS. <br /> TANK #1 : REG UNLEADED TYPE: STEEL RATE: . 006080 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: . 10 <br /> TANK IS TIGHT. <br /> TANK #2 : SUPER UNLEADED TYPE: STEEL RATE: . 007460 G.P.H. LOSS <br /> ULLAGE: PASS SIGNAL/NOISE: . 13 <br /> TANK IS TIGHT. <br /> TANK #3 : DIESEL FUEL 2 TYPE: STEEL RATE: . 000723 G.P.H. LOSS <br /> ULLAGE: PASS SIGNAL/NOISE: . 12 <br /> TANK IS TIGHT. <br /> EQUIPMENT: USTEST <br /> OTTL# 97-1143 <br /> OPERATOR: LYLE D. NIMMO SIGNATURE: <br /> ZANE A. NIMMO, Trainee t <br />