Huffco Manufacturing
<br /> May 13, 2009
<br /> Page 4
<br /> Re: 4447 S. Airport WY
<br /> Electrical- The following violations listed are for the interior, exterior, and roof of the
<br /> building that were found by City of Stockton Electrical Inspector John Freitas during a joint
<br /> inspection of the above listed property on Friday May 8, 2009 with the City of Stockton Fire
<br /> Dept., Neighborhood Services Dept., and Building Inspector Blake Froberg: This list is a
<br /> component of the notice of Violation and is issued to give more restrictive and concise
<br /> directions for compliance.
<br /> 1 . All extension cords shall be removed and not used as permanent wiring. All
<br /> electrical wiring shall be an approved permanent hardwired method as allowed by
<br /> code.
<br /> CFC 605.5, CEC Article 400.8
<br /> 2. All electrical enclosures listed below shall be properly closed after the interiors have
<br /> been thoroughly cleaned/removed of all dust, debris, and rubber dust. Install the
<br /> approved covers and all junction boxes, disconnects, panels, equipment,
<br /> transformers, switches, outlets, CFC 605.6, SMC 14-402.1(b)4
<br /> 3. Submit plans and obtain permits and inspections for all equipment, lighting, outlets,
<br /> feeders, switches, related electrical, etc. that has been installed without approved
<br /> plan, permits, and inspections. SMC 13-301(a)
<br /> 4. All equipment shall be listed by an approved third party testing agency. CEC 90.7
<br /> 5. All electrical systems, machinery, outlets, fixtures, electrical distribution systems,
<br /> panels, feeders, junction boxes, and related electrical to be properly installed and
<br /> maintained on a regular basis as per code requirements. SMC 14-402.1(b)4
<br /> 6. Remove all abandoned and un-used electrical wiring, fixtures, panels, conduits,
<br /> raceways, enclosures, disconnects, switches, etc. throughout the entire building.
<br /> SMC 14-402.1(b)4
<br /> 7. Use an approved hard wire wiring method to supply and connect power to all
<br /> machines and equipment as per code requirements. SMC 14-402.1(b)4
<br /> 8. Properly install all wiring on all machinery and equipment as per code and per
<br /> manufacture's requirements. SMC 14-402.1(b)4
<br /> 9. Properly install branch feeders to all machinery and equipment as per code
<br /> requirements. SMC 14-402.1(b)4
<br /> 10.Install an approved service disconnect switch for all machines and equipment as per
<br /> code requirements. CEC 670.48
<br /> 11 .Properly replace and repair all damaged ( including fire damaged ) electrical wiring,
<br /> lighting, conduits, raceways, outlets, disconnects, panels, etc. on the rear exterior of
<br /> the building. SMC 14-402.1(b)4
<br /> 12.Properly label all branch circuit breakers in all panels and services. CEC 408.4
<br /> 13. Install the proper complete panel covers and breaker fillers in all open panels.
<br /> CEC 408.7