Laserfiche WebLink
LIAR 0 7 2016 <br /> 4. PIPING SUMP TESTING <br /> JF <br /> Test Method r)evcloped By: p Sump Manufacturer ® Industry Standard ❑ P�ro,jV*,( aa, W6W,AiT <br /> ❑Other(Specilj�) <br /> Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> ❑Other(Specib) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br /> STP Sump#87 <br /> Sump Diameter: 42" <br /> Sump Depth: 63" <br /> Sump Material: Fiberglass <br /> Height from Tank Top to Top of <br /> Highest Piping Penetration: 14" <br /> Height from Tank Top to Lowest 26" j <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Good <br /> Portion of Sump Tested' 2"above piping <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑ Yes❑No ®NA <br /> product and water)?* <br /> Turbine shutdown response time N/A <br /> Is system programmed for fail-safe 0 Yes❑No ®NA <br /> shutdown?* <br /> Was fail-safe verified to be ❑ Yes❑No ®NA <br /> operational?' <br /> Wait time between applying <br /> pressure/vacuum/water and starting 30 minutes <br /> test: <br /> Test Start Time: 2:10 pm <br /> Initial Reading(Ri): 4.4691 <br /> Test End Time: 3:26 pm <br /> Final Reading(RF): 4.4693 <br /> Test Duration: 16 min. <br /> Change in Reading(RF-Ri): 0.0002 <br /> Pass/Fail Threshold or Criteria: +/-0.002" <br /> Test Result: El Pass ❑ Fail <br /> Was sensor removed for testing? ®Yes C]No[INA <br /> Was sensor properly replaced and ®Yes❑ No❑NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to tesling, and recommended fnl/nw-up.for.Jailed lesis) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> Replaced test boot in 87 STP. <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*) is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />