My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
INSTALL 2002
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
M
>
MANTHEY
>
3408
>
2300 - Underground Storage Tank Program
>
PR0517521
>
INSTALL 2002
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/22/2019 11:38:25 AM
Creation date
5/8/2019 11:47:47 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
INSTALL
FileName_PostFix
2002
RECORD_ID
PR0517521
PE
2361
FACILITY_ID
FA0013484
FACILITY_NAME
FOOD 4 LESS FUEL CENTER*
STREET_NUMBER
3408
STREET_NAME
MANTHEY
STREET_TYPE
RD
City
STOCKTON
Zip
95206
APN
16422011
CURRENT_STATUS
01
SITE_LOCATION
3408 MANTHEY RD
P_LOCATION
01
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
202
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Atmefflkt <br /> DualoyD Installation <br /> Guidelines for Service <br /> Station Layout <br /> using Dualoy 3000/1-fiberglass <br /> piping systems <br /> Introduction Adhere to the methods illustrated in the following photographs when installing Dualoy <br /> 3000/L buried fuel handling piping systems. <br /> Petroleum piping <br /> i •Maintain a minimum 6112"distance between <br /> parallel lines and between the trench side <br /> wall and the piping.•Piping runs must be <br /> straight.•Use Phil-Tete styrofoam pipe <br /> spacers to support the pipe.•Maintain a <br /> minimum 2'h"vertical clearance between <br /> lines at crossovers.•Keep the trench <br /> bottom clean and free from debris. _ •, <br /> •Remove the surface gloss bylight sanding <br /> to a uniform length at the ends of each piece <br /> of containment pipe before installing the <br /> containment fittings.•Uniform gloss <br /> removal makes it easier to determine that the <br /> containment pipe is inserted to a constant <br /> 1 Z inch depth in the containment fittings. <br /> UUnderwriters C <br /> ® L Laboratories Inc.® L <br /> tso•9oo, <br /> z <br /> 'RMtr ATW FIRM <br /> FP626(7/95) <br />
The URL can be used to link to this page
Your browser does not support the video tag.