PLASTEEL UNDERGROUND TANK <br /> APPENDIX B <br /> INTERSTITIAL VACUUM TEST (IVT) <br /> 1.0 Introduction: This test method has been developed by down on the ELUTRONO jacketed tank may require <br /> PLASTEEL INC.to meet the E.P.A.Alternate(Non-Volumetric)Tank Tightness reiteration due to the slow nature of air movement in the <br /> test procedures. The IVT has been verified by a third party to be capable of interstitial space. <br /> detecting a 0.1 gal/hr leak rate with a probability of detection of 100%when all <br /> of the testing criteria are met.The false alarm rate for a tight tank is less than 5.4 ensure a vacuum has been established,the gauge must <br /> re <br /> 5%.It is impossible to maintain a steady vacuum if a leak is present.This test is read 10"hg.for three(3)hours without any decrease on <br /> not necessary to attain the PLASTEEL@ tank warranty.This test is offered as a the gauge before proceeding with 5.6. Contact the <br /> stand alone leak tightness test method. factory if the vacuum cannot be established per this <br /> paragraph. <br /> 2.0 Aoolication: The IVT is applicable to the PLASTEEL@ 5.5 Complete sections II and 111 of the Certificate of <br /> ELUTRONO (jacketed) Double-wall tank and the PLASTEEL® Composit Tightness Test. <br /> Double-wall tank.For compartmented tanks,consult the factory for the test time. 5.6 Refer to the Test Time Table (Figure 6.0) to determine <br /> 3.0 Authority: The Jurisdiction Having Authority (JHA) will determine the correct minimum time period for a valid test. <br /> whether the double-wall UST must be subject to a leak tightness test before Begin timing the test after completing 5.4. Record the <br /> placing the UST in service. nominal tank capacity, primary tank product and <br /> required test hours in Part IV of the Certificate. <br /> 4.0 Pre-Delivery Procedure: 5.7 After the required test time has passed, observe the <br /> 4.1 Read and understand the PLASTEEL@ Tank Installation gauge reading and record the reading,date and time of <br /> instructions and Appendix B before attempting the interstitial day in Part IV of the Certificate. <br /> vacuum test. Contact the PLASTEEL@ tank manufacturer if you 5.8 Test Conclusions:The tank has passed the leak tightness <br /> have any questions. test when the final gauge reading has not decreased from <br /> 4.2 Consult the PLASTEEL@ tank manufacturer before the tank is the initial gauge reading of 10"Hg.If other observations <br /> shipped to ensure that the tank is delivered with the test gauge are made,consult the tank manufacturer. <br /> assembly. This assembly is an optional piece of equipment <br /> supplied by the tank manufacturer. Test Time Tables: The table in Figure 6.0 lists the <br /> 4.3 Prior to shipment from the factory, you may request that the minimum test period(in hours) to perform a valid IVT with a <br /> manufacturer deliver the tank with the vacuum established. dry (air only) primary tank. The IVT test may be performed <br /> with gasoline,diesel or water in the primary tank. Consult the <br /> 4.4 Upon delivery, the delivery document will indicate the correct PLASTEEL@ tank manufacturer for the specific test time for <br /> vacuum gauge reading. Call the factory if the gauge reading does these situations. <br /> meet the gauge reading specified on the delivery document. <br /> 4.5 To maintain the vacuum during the unloading and installation TEST TIME TABLE:DRY PRIMARY TANK <br /> phases, extreme care must be taken to ensure the IVT gauge <br /> assembly is not jarred, struck or moved in any manner. Call the CAPACITY JACKETED COMPOSIT <br /> factory for instructions if the vacuum has decreased. (GALS.) (HOURS) (HOURS) <br /> 5.0 Test Procedures: 500 4.0 4.5 <br /> 5.1 If the vacuum was established at 1,000 4.0 5.5 <br /> delivery and has not decreased 2,000 4.0 8.0 <br /> QUICK �� during the unloading and 3,000 4.0 9.0 <br /> DISCONNECT BUTTERFLY g g <br /> (Optional) VALVE installation phases, you may <br /> / by-pass 5.2 and 5.3 4,000 a.o 9.5 <br /> / <br /> /// 5.2 Install the vacuum gauge test 5,000 4.0 10.5 <br /> assembly (see Fig. 5.0) in the 6,000 4.0 11.0 <br /> monitor access NPT coupling on 8,000 4.0 13.0 <br /> the tank top centerline. Ensure 10,000 4.0 14.5 <br /> r f that any additional monitor <br /> access couplings are properly 12,000 4.0 15.5 <br /> INTERSTITIAL sealed with threaded plugs. <br /> MONITOR 15,000 4.0 17.5 <br /> = <br /> FITTING 5.3 Connect the vacuum pump to 20,000 4.0 20.5 <br /> 1 the test gauge assembly and <br /> draw down to 10" hg. Record 30,000 4.0 37.5 <br /> FIGURE 5.0: VACUUM GAUGE initial gauge reading, date, and 40,000 4.0 45.5 <br /> TEST ASSEMBLY(TYPICAL). time of day in Part IV of the <br /> CURACY:ASME(ANSI)GRADE B, Certificate. The initial pump 50,000 4.0 53.0 <br /> 2%,0.30"Hg,with 1"Hg GRADUATIONS. FIGURE 6.0 <br /> INSTALL RZESZOW INDUSTRIA ACERO HALL TANK CO. JOOR MFG. K&T STEEL METAL PRODUCTS TANX INC. SHINWON INDUSTRY TANOUES GUMEX TECNOECO ARGENTINA <br /> Rzeszow,Poland Quito,Ecuador N.Little Rock,AR Escondido,CA Twin Falls,ID Suwanee,GA Claremont,NH Seoul,Korea Torreon,Mexico Buenos Aires,Argentlna <br /> (501)9453211 (760)745.0971 (208)733-2554 (770)945.8383 (603)543.1272 <br /> INDUSTRIAS CORREAGUA JAPAN STEEL WORKS Fax(501)9454477 Fax(760)746-9515 Fax(208)733-7239 Fax(770)932.5671 Fax(603)543.1270 TECNOECO CHILE TVG MEfALURGICA RIMA <br /> Panama,Panama Tokyo,Japan Santiago,Chile Tab,Hungary Guaira,Brazil <br /> APP.B.03.98 <br />