Laserfiche WebLink
OCTOBER 14, 2002 <br /> j ARCO FAC 8313 <br /> PETCON 1100 S MAIN ST IINOUSTRIAL <br /> TECHNOLOGIES MANTECA, CA <br /> INC. <br /> SCOPEDF WORK <br /> TO REPAIR THESE FAILED COMPONENTS <br /> 87, 89, 91 SECONDARY LINES <br /> 87, 99, 91 TURBINE SUMPS <br /> i 87, 89, 91 FILL SUMPS <br /> 87-1, 87-2, 89 SPILT. BUCKETS <br /> 118, 2/5, 3/4, 7/12, 8/11, 9/10 DISPENSER PANS <br /> 1. REPAIR SECONDARY LINES <br /> 14118 S.Inglewood Avenue a. INSTALL/ REPLACE 3"x2" REDUCER BOOTS TO TEST <br /> Hawihcme,CA 90250 b. RETEST <br /> c, IF NEEDED, TIGHTEN CLAMPS, RESEAT BOOTS, <br /> 73108799991 d, IF NEEDED, EXCAVATE PORTION OF TANK SLAB AND <br /> F 310 679 9994 REPAIR PIPING PER MANUFACTURER'S <br /> RECOMMENDATIONS. <br /> e. IF NEEDED, REPLACE PENETRATION BOOTS ON <br /> DISPENSERS. <br /> pfifieii�petcohtr�ch.com <br /> 2. REPAIR LEAKS IN TURBINE/ FILL SUMPS <br /> www,peloanteah,acm a. TIGHTEN CLAMPS RESEAT BOOTS <br /> b. INSTALL SSI WEAVER PENETRATION FITTINGS WHERE <br /> { PIPING / CONDUIT PASSES THROUGH SUMP WALL, <br /> ' c. IF NEEDED, SEAL SUMP COLLARS WITH FIBERGLASS <br /> AND RESIN <br /> E <br /> 3. REPAIR SPILL BUCKETS <br /> a. CLEAN / REPLACE DRAIN VALVES <br /> ! b. CLEAN / REPLACE GASKETS <br /> c. IF NEEDED, REPLACE SPILL BUCKETS TO MATCH <br /> EXISTING, <br /> 4. REPAIR UDCs <br /> a. TIGHTEN BOOTS <br /> b. REPLACE BOOTS IF TORN <br /> c. INSTALL SSI WEAVER PENETRATION FITTINGS WHERE <br /> PIPING I CONDUIT PASSES THROUGH DISPENSER PAN <br /> WALL. <br /> d. it WEEDED, EXCAVATE PORTION OF TANK SLAB TO <br /> TIGHTEN / REPLACE UNDERGROUND PENETRATION <br /> BOOTS <br />