Laserfiche WebLink
SWRCB,January 2002 Page 5 of <br /> 7. UNDER-DISPENSER CONTAINMENT(UDQ TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> UDC#1&6 UDC#2&5 UDC#3&4 UDC#7&12 <br /> UDC Manufacturer: Western Fiberglass Western Fiberglass Western Fiberglass Western Fiberglass <br /> UDC Material: Fiber lass Fiberglass Fiberglass Fiberglass <br /> UDC Depth: 29" 29''/z" 30" 311/4" <br /> Height from UDC Bottom to Top 12" 12" 13" 13" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 8" 8" 8" 8" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry Dry Dry <br /> testing: <br /> Portion of UDC Tested Water Level 14" Water Level 14 '/Z" Water Level 15 ''/s" Water Level 16''/s" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both X Yes No ❑NA X Yes No ❑NA X Yes No ❑NA X Yes No ❑NA <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail- X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA <br /> safe shutdown?* <br /> Was fail-safe verified to be Yes X No ❑NA Yes X No ❑NA Yes X No ❑NA Yes X No ❑NA <br /> op erational?* <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> water and starting test <br /> Test Start Time: 12:55 12:45 12:30 11:45 <br /> Initial Reading(RD: .001 .001 .001 .001 <br /> Test End Time: 1:25 1:15 1:00 12:15 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RrR,): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30Minutes .005/30 Minutes <br /> Test Result: X Pass ❑Fail X Pass 0 Fail X Pass 0 Fail X Pass ❑Fail <br /> Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA <br /> Was sensor properly replaced and X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> ' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to M of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />