Laserfiche WebLink
Veeder-Root Sensor Applit_,on Guide <br /> Sump Sensor <br /> The Piping Sump Sensor is installed in a tank piping sump and will detect the presence of a liquid. Liquid level is <br /> monitored by a float/magnetic reed switch sensing system. <br /> Sensor Detection Capabilities - Alarm Conditions <br /> • Fuel alarm is triggered when liquid reaches a nominal height of 1-inch. <br /> • An open sensor triggers a Sensor Out alarm. <br /> Operating Capabilities <br /> • Operating temperature range: 0 to+60°C. <br /> • Storage temperature range: -40 to+70°C. <br /> • Sensor dimensions: 12" high, 1.9"diameter. <br /> Sensor/Cable Length Configurations <br /> • Sump Sensor w/12 foot cable - Form Number 794380-2081 <br /> • Sump Sensor w/30 foot cable - Form Number 794380-2091 <br /> 'Sensors 794380-208 and-209 are direct replacements for sump sensor 794380-205. <br /> Sensor Interface Module <br /> • TLS-350 series consoles (except TLS-350J)- Interstitial/Liquid Sensor interface module (P/N 329358-001) <br /> accepts up to 8 sensors (a maximum of 64 sensors could be monitored by the console). <br /> • TLS-350J console-3 sensors max. <br /> • TLS-300/PC-300 series consoles (no interface module required)-8 sensors max. <br /> • ILS-350 console-A Two-Wire Module(P/N 329675-001) accepts up to 4 sensors(a maximum of 16 sensors <br /> could be monitored by the console). <br /> • TLS-450- USM (P/N 332812-001), accepts up to 16 sensors <br /> Console Software Compatibility <br /> • TLS-350 series/TLS-300 (Version 1 or later) <br /> • ILS-350 (All) <br /> • TLS-450 (All) <br /> IMPORTA Compatible FuelskN <br /> —Existing conduit <br /> or piping <br /> • Unleaded gasoline <br /> • Unleaded with up to 5%methanol, •:.- <br /> 15%ethanol,or 15%MTBE -� !p Product <br /> • Leaded gasoline Cable to junction boxy Cable to junction pipe <br /> • Diesel and seal-off box and seal-off <br /> • Kerosene <br /> • Jet fuel <br /> • Aviation gasoline <br /> 'Sump sensor should: <br /> 7.Rest on the base of the sump. <br /> Related Sales Literature 2.Be positioned as close to outer <br /> wall as possible. Sump sensor' <br /> Visit our website at www.veeder.com 3.Be mounted in a true vertical (installation examples) <br /> position. <br /> for more information on Veeder-Root 4.Be installed only in a dry sump. <br /> products and services. (sump base <br /> 7VI <br /> Typical <br /> 5 <br />