Laserfiche WebLink
TANKNOLOGY - UNDERGROUND LEAK DETECTION SYSTEM (V3. 12) Page 12 <br /> HBU9310-IVE340242-94295-02 Oct 19, 1993, 01:32 <br /> k,,y d IJ—TE=a_--F 'TES3T SflJ1� 1h'1C-NF.^'v" <br /> TEST DATE Oct 15, 1993 <br /> START TIME : 01 : 32: 59 <br /> CLIENT EXXON <br /> LOCATION NAME <br /> LOCATION CODE : 701.26 <br /> TANK CONFIGURATION : Tandem <br /> TANK CONTENTS SUPREME/PLUS <br /> TANK; NUMBER 02 0 <br /> TANK. DIAMETER 95 95 in <br /> TANK. CAPACITY 10000 t0000 G <br /> TANK: MANUFACTURER <br /> TANK MATERIAL- Steel Steel <br /> TANK REGISTRATION .N <br /> TANK DATE INSTALLED <br /> INITIAL. DIPPED FUEL LEVEL 61 . 00 62. 00 in <br /> INITIAL DIPPED WATER LEVEL 0. 50 0. 50 in <br /> POST PUMPING WATER LEVEL 2. 50 1 . 30 in <br /> T"d-�h M 1-- -1-E_:S�T E<`1_81_J E--F <br /> TEST INITIAL WATER LEVEL_ 0. 58 0. 50 in <br /> TEST FINAL._ WATER LEVEL : 0. 58 0. 30 in <br /> WATER INGRESS 0. 00 0. 00 in <br /> BUBBLE SIGNATURES No No <br /> VACU-TELT -FEST RESULT : Passed Passed <br /> COMMENTS: <br /> CONCLUSION: <br /> TANKS TESTED TIGHT., <br /> L_ 11',11•; "l-EE C-3 IF 1 :,E- r-`RJ 1_T <br /> TEST RATE TEST PATE <br /> LINE RESULT PRESSURE OF LOSS _ ._ RESULT PE:ESSURE OF LOSE= <br /> #1 Passed so PSI 0. 00 GPH passed SO PSI 0. 00 SPH <br /> #2 <br /> #3 <br /> #4 <br /> #5 <br /> #6 <br /> COMMENTS: <br /> CONCLUSION: <br /> This test was conducted in accordance with U.S. EPA Rule 40 CFR Parts 2B0 and 281, <br /> HOU9310-IVES40242--94 95402 <br /> U.NIL&SAN VACU-TECT(tm) Test Number <br />