Laserfiche WebLink
MAR-23-2010 09:56 Service Station Systems 4oe 938 egee P.11/11 <br /> 11. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not'fested ❑ <br /> Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engincer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ® Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: lncon Sump Tester Equipment Resolution: +/-0.002" <br /> Fill Sump k 87 Fill Sump#91 Fill Sump#Diesel VENT Sump <br /> Sum Diameter: 42" 42" 42" 36" <br /> Sump Depth: 74" 74" 74" 20" <br /> Height from Tank Top to Top of 18" 18" 18" 8" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 32" 32" 32" 3" <br /> Electrical Penetration: <br /> Condition of sump prior to Good Good Good Good <br /> testing: <br /> Portion of Sump Tested 2"above piping 2" above pi2inE 2"above piping 2"above piping <br /> Sump Material: Fiber lass Fiberglass Fiberglass Fiberglass <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes 30 minutes 30 minutes 30 minutes <br /> starting test: <br /> Test Start Time: 9:43 am 9:43 am 9:43 am 10:30 am <br /> Initial Reading R, ; 3.9947 4.3611 4.9535 2.5582 <br /> Test End Time: 9:58 am 9:58 am 9:58 am 10;45 am <br /> Final Reading(Rr); 3.9565 3.9700 4.9189 2.5574 <br /> Test Duration: 15 min. 15 min. 15 min. 15 min, <br /> Chan aii Reading(RF-Rt): -0.0382 -0.3911 -0.0346 -0.0008 <br /> Pass/Fall Threshold or Criteria: +/_0,002" +/.0.002" +/-0.002" +/-0.002" <br /> Test Result: 0 Pass © Fail 0 Pass 181 Fail ❑ Pass 21 Fail Q Pass ❑Fail <br /> Is there a sensor in the sump? —&Yes ❑No N Yes ❑No M Yes ❑No ®Yes ❑No <br /> Does the sensor alarm when <br /> either product or water is ❑Yes ❑No®NA ❑Yes❑No®NA p Yes❑No®NA ❑ Yes❑No®NA <br /> detected? <br /> Was sensor removed for testing? ®Yes ❑No❑NA M Yes❑No❑NA N Yes❑No❑NA ®Yes❑No ❑NA <br /> Was sensor properly replaced and ®yes❑No❑ NA ®Yes❑No❑ NA ®Yes p No❑ NA ®Yes ❑No❑ NA <br /> verified functional after testing? <br /> Comments— (Lclude information on repairs made prior to testing, and recommended/allow-up./or/ailed tests) <br /> "Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br /> All fill sumps failed. Torn penetration boots <br /> TOTAL P.11 <br />