Laserfiche WebLink
CONTACT I- 'OR MORE INFORMATION! <br />tern5555 Skylane Blvd., SL A / Santa Rosa, CA 95403 <br />lass Ph: (800) 688-3375 / Fx: (800) 700-1188 <br />www.westernfg.com <br />product dispensers. Note: 1 1/2" I.D. Co -Flex piping is typically suitable for <br />continuous operation of up to six (6) product dispenser nozzles. <br />Suction system routing requires direct runs where each dispenser is <br />connected to the tank sump via it's own pipe line. <br />Co -Flex flexible piping may be installed in our approved chase conduit -4" <br />Rockguard (PI4531). After installation of conduit, the flexible pipe is pulled <br />through the conduit by threading a cap with an "I" bolt to the pipe <br />termination and attaching a rope or cord. <br />7f9 <br />PIPING TRENCHES: <br />Trenches should be at least twice the width of all piping and/or conduits <br />to be installed within. One pipe diameter spacing between each pipe run <br />is required. <br />Piping systems requiring "fall" should have a minimum of 1% or 1/8" per <br />linear foot from pipe run termination point back to the tank sump(s). <br />The recommended backfill and trench bed material is rounded pea <br />gravel 1/8" to 3/4" in diameter. Crushed stone, 1/8" to 3/4", and/or river <br />sand may be used if washed and it is free flowing. <br />A 6" bed of recommended backfill material, free from any debris, is <br />placed in the piping trench prior to installation. <br />Page 6 of 38 <br />