Laserfiche WebLink
CONTACT I` 'OR MORE INFORMATION! <br />stern 5555 Skylane Blvd., SL A / Santa Rosa, CA 95403 <br />rg)ass Ph: (800) 688-3375 / Fx: (800) 700-1188 <br />www.westernfg.com <br />Tank Sump <br />INSTALLATION INSTRUCTIONS <br />Please read all instructions completely prior to installation. These instructions <br />do not supersede local laws and regulations. Always comply with local <br />requirements. <br />PRE -BONDING SURFACE PREPARATION: <br />BE SURE TO WEAR A DUST MASK! After positioning sumps onto tank collar or <br />after placing reducer on sump riser tube, use disc sander, with medium to <br />heavy grit sand paper, to scuff up all seam areas a minimum of 4" each side <br />of the point where the components join. It is very important that this be done <br />fully, as the bonding materials will not adhere to any surface that has not <br />been sanded. Brush sanding dust from seam areas. <br />SEAM LAMINATIONS: <br />CAUTION: Always wear gloves when handling fiberglass bonding materials! <br />Use one plastic bucket with acetone to clean roller, brushes and squeegee. <br />Return tools to this bucket between use to prevent bonding materials from <br />drying on them. BE SURE TO SHAKE THE ACETONE OUT OF TOOLS BEFORE RE- <br />USE! <br />Lay out fiberglass materials at each seam to be bonded. (1 x 3 oz FRP mat for <br />collar attachment. 1 x 3 oz and 1 x 18oz woven roving material for direct <br />attachment.) <br />IV <br />TAW <br />TMMC <br />Page 28 of 38 <br />SRtUIJ(.ERR <br />SAND/BOND AREA <br />SAND/BOND AREA <br />