American Paving System, Inc. <br /> 550 Gallon Used Oil Tank <br /> Certified UL 142 #466558 <br /> South End <br /> 0.124 0.123 0.124 0.125 0.123 <br /> 0.099 0.123 0.100 <br /> 0.124 <br /> 0.124 0.123 0.124 0.124 0.123 <br /> 0.123 0.124 0.122 0.124 0.124 <br /> East Side 0.124 0.123 0.124 0.124 0.123 West Side <br /> 0.123 0.124 0.123 0.122 0.124 <br /> 0.124 0.124 0.122 0.124 0.123 <br /> 0.123 0.122 0.123 0.124 0.124 <br /> 0.124 <br /> 0.124 0.123 0.124 <br /> 0.124 0.123 0.124 1 0.123 0.124 <br /> North End <br /> Certified Non-destructive metal thickness testing was performed on May 17, 2019, <br /> using a certified Danatronics EHC 09 double echo solid metal thickness ultrasound <br /> test unit. Thickness calibration was performed and passed prior to conducting the <br /> certified non-destructive metal thickness evaluation. Reported measurements are the <br /> average metal thickness for the tank ends and sides. Each set of data readings is <br /> comprised of 15 A point readings averaged over a 1 square foot area. Average tank <br /> end metal thickness is 0.124 inches. The average tank side metal thickness is 0.124 <br /> inches. No metal thickness defects were observed and the Certified UL 142 550 <br /> Gallon Used Oil storage tank passed its certified non-destructive integrity testing. <br /> Gary Reeves <br /> Steel Tank Insitute Level 11 , °51(012( <br /> Sp001 # 11111 ` <br /> Non-Destructive UT Level III <br /> NDT-UT#0001 <br /> ASNT-TC-1A#073128 <br /> REA # 30349 <br /> ICC #8019664 May 17, 2019 <br />