Laserfiche WebLink
American Paving System, Inc. <br /> 17333 Comconex Road <br /> Manteca, CA 95354 <br /> 180 Gallon Rando HD 46 Tank <br /> West <br /> 0.119 0.118 0.119 0.120 <br /> 0.118 0.119 0.118 0.119 <br /> 0.119 0.120 0.119 0.120 <br /> 0.118 0.119 0.118 0.119 <br /> 0.118 0.119 0.118 0.1190.118 0.120 <br /> 0.120 0.118 0.119 0.118 0.119 0.119 <br /> 0.118 0.119 0.120 0.119 <br /> 0.119 0.120 0.118 0.118 <br /> 0.120 0.118 0.119 0.120 <br /> 0.119 0.120 0.118 0.119 <br /> East <br /> Non-destructive metal thickness testing was performed utilizing a Certified <br /> Danatronic EHC-09DL-CW Digital Ultrasound thickness gauge. Calibration of the <br /> certified non-destructive gauge was performed on May 17, 2019, and prior to <br /> conducting the certified testing of the 180 Gallon Hydraulic Oil tank. Non- <br /> destructive testing consisted of up to 15 A point measurements in every square <br /> foot throughout the lower half of the tank. The average measurements are <br /> reported in the boxes and no metal defects were observed. The 180 Gallon <br /> Hydraulic Oil Tank passed it's certification testing. System is classified as a <br /> Category Ill system. <br /> Gary Reeves <br /> As k Ins <br /> Cs <br /> Steel Tank Institute 5� a� <br /> Level II SP001 #11111 <br /> NDT-UT Level Ill #001 <br /> ASNT-TC-1A #073128v0; <br /> Certified Environmental Professional May 17, 2019 <br />