Laserfiche WebLink
The following is an itemized list of aboveground petroleum storage act violations that <br /> have not been addressed for ATS MANTECA as of July09, 2019. <br /> Open violations from April 26, 2019 inspection <br /> Violation #706 -Failed to provide and maintain adequate secondary containment. <br /> The two 140 gallon motor oil tanks were observed with insufficient secondary containment. Two 55 gallon drums of <br /> motor were observed off of the secondary containment pallets. All bulk storage tanks must be provided with a <br /> secondary means of containment for the entire capacity of the tank and sufficient freeboard to contain precipitation. <br /> Immediately provide sufficient secondary containment for this and all other tanks at this facility. <br /> Violation #717 -Failed to promptly correct visible discharges and/or remove accumulations of oil in diked <br /> areas. <br /> The 140 gallon tank of 15W-30 was observed with a leaking hose. Visible discharges which result in a loss of oil <br /> from a container, including but not limited to seams, gaskets, piping, pumps, valves, rivets, and bolts, must be <br /> promptly corrected. Immediately fix the hose and provide proof to the EHD. <br /> Page 1 of 1 <br />