Laserfiche WebLink
1 <br /> M(6111VE III Ills <br /> LABORATORIES INC <br /> QC Summary <br /> Client Hydro Environmental Technologies <br /> Project Central California Traction Co Matrix water <br /> Method 8260 9,9-DCE Benzene TCE Toluene Cl-Benz <br />' Recovery % QC Limits (60-120) (60-120) (60-120) (60-120) (60-120) <br /> RPD- % QC Limits <30 <30 <30 X30 <30 <br />' Date Analvzetf 7118100 <br /> Spike Level (ug/L) 100 100 100 100 100 <br /> Sample Amount 00 00 00 00 00 <br /> LCS Amount Found 11 1 98 96 9 5 102 <br /> LCSD Amount Found 108 104 97 99 101 <br />' LCS Recovery 111 2 975 959 954 101 7 <br /> LCSD Recovery 1081 1036 973 987 101 1 <br /> RPD - % 28 61 14 34 06 <br />' Date Anal zed 7119100 <br /> Spike Level (ug/L) 100 100 100 10 0 100 <br /> Sample Amount 592 00 00 00 00 <br /> MS Amount Found 684 9 5 90 93 91 <br /> MSD Amount Found 71 6 104 95 101 96 <br /> MS Recovery 922 951 897 929 912 <br /> 95 8 <br /> MSD Recovery 124 1" 1039 948 101 1 <br />' RPD - % 295 88 55 85 49 <br /> MSD recovery outside QC range, no corrective action taken <br /> Calibration verification was within acceptable limits <br /> TEG07'1800 <br />' Page 8 of 8 <br /> 148 SD VINEWOOD STREET u ESCONDIDO CA 92029 e PHONE [760] 735-3208 o FAX (760) 735-2469 <br />