Laserfiche WebLink
MONITORING AND REPORTING PROGRAM <br /> DEFENSE DEPOT TRACY <br /> SAN JOAQUIN COUNTY <br /> AIR STRIPPER MONITORING: <br /> The air stripper monitoring program shall consist of the sampling of both the <br /> influent and the effluent waste streams per the following schedule. Influent <br /> samples shall be collected from the inlet sampling port of the air stripper <br /> facility. Effluent samples shall be collected from the sampling port at the base <br /> of the air stripper sump. Time of collection of a grab sample shall be recorded. <br /> Type of Sampling <br /> Constituents Units Sample Frequency <br /> Volatile Organics µg/l Grab Weekly <br /> (Methods 8010 and 8020) <br /> Specific Conductivity umhos/cm Grab Weekly <br /> PH pH Units Grab Weekly <br /> Temperature ° F/°C Grab Weekly <br /> Volatile Organics µg/l Grab Quarterly <br /> (Method 8240) <br /> Total Petroleum HCs mg/l Grab Quarterly <br /> (Method 418. 1) <br /> Pesticides - PCBs µg/l Grab Quarterly <br /> (Method 8080) <br /> Metals mg/l Grab Quarterly <br /> (Method 6010) <br /> Arsenic mg/l Grab Quarterly <br /> (Method 7060) <br /> Mercury mg/l Grab Quarterly <br /> (Method 7471) <br /> Selenium mg/l Grab Quarterly <br /> (Method 7740) <br /> Total Volume of gallons Meter Weekly <br /> Water Treated <br /> Flow Rate at Time gpm Meter 'leekly <br /> of Sampling <br /> Average Flow Rate gpm Meter Weekly <br /> (since last sampling) <br /> Pressure at Time psig Meter Weekly <br /> of Sampling <br />