Wongdeff <br /> From: Wong,Jeff <br /> Sent: Wednesday, May 15, 2019 4:29 PM <br /> To: 'Garrett Readler' <br /> Cc: Kith, Michael; Dan Hughes; Kevin Coleman; Naidu, Muniappa <br /> Subject: RE: LBA Schulte - 14900 W. Schulte <br /> Garrett: <br /> Thanks for the clarification at today's GoToMeeting. EHD has the following comments to your proposal below: <br /> 1) Schedule inspection with EHD to verify removal of the 5' piece of 4" piping and plugging the remaining pipe with <br /> concrete as described below, to the effect that drainage of both buildings are completely separate from the <br /> septic system and cannot be connected. <br /> 2) Schedule inspection with EHD to verify permanent removal/plugging of the drain of the exterior concrete <br /> basins where the fuel tanks will be sitting, so no fuel can ever enter the drains inside the two concrete buildings. <br /> 3) Schedule inspection with EHD to verify the floor drains inside the two concrete buildings and the two 2'x2'boxes <br /> are indeed "closed", and there are no other outlets in these boxes. <br /> 4) Before any hazardous materials/waste can be stored onsite,the owner/operator must report it to the California <br /> Environmental Reporting System (CERS) at cers.calepa.ca.gov/ <br /> - CERS is applicable on this site since there are the two diesel tanks outside the concrete buildings (each <br /> greater than 55 gallons). Demonstrate to EHD that the "Emergency Response/Contingency Plan" section <br /> (Section D) in CERS has been updated. Please notate in the section that the "floor drains", 'Tx2'boxes", and <br /> any subsurface piping, drains, or containment will be kept empty at all times, and any release will be cleaned <br /> up and the waste properly disposed in accordance to regulations immediately. Please be aware that storage <br /> of hazardous materials/waste in a subsurface containment is prohibited except in a permitted underground <br /> storage tank system. <br /> Please schedule these inspection(s)with me as soon as possible. EHD will not agree to Final Occupancy and the <br /> complaint will remain open until these conditions have been addressed. <br /> Best Regards, <br /> Jeff <br /> From: Garrett Readler<greadler@kierwright.com> <br /> Sent: Wednesday, May 15, 2019 11:55 AM <br /> To:Wong,Jeff<Jwong@sjgov.org> <br /> Cc: Kith, Michael <mkith @sjgov.org>; Dan Hughes<dhughes@netdevco.com>; Kevin Coleman <br /> <kcoleman@netdevco.com> <br /> Subject: RE: LBA Schulte- 14900 W. Schulte <br /> Importance: High <br /> Jeff, <br /> Per our conversation this morning I have updated the exhibit to further clarify exactly what we are <br /> proposing. Currently, each building in the fire yard has a floor drain that is connected to a 4" sewer line <br /> that connects to the 8" sewer line in the drive aisle. The 8" sewer line connects to the septic tank/leach <br /> field. We are proposing to constructed a 2' x 2' concrete box over the 4" sewer lines exiting each building, <br /> and then disconnecting the 4" sewer lines down stream of the concrete boxes. The plan will be to remove <br />