Laserfiche WebLink
1 <br /> 161?126196 <br /> QUALITY CONTROL REPORT DHS Certification #1400 <br /> Volatile Analyses <br /> Client: DEL TECH Date Received: 17/20/96 <br /> t10624 OLIVE AVE Date Started: : 12!23196 <br /> OAKDALE, CA 95361 Date Complete: 17126/96 <br /> ' ATTN: DON LIGHT <br /> Lab Report#: H6122001 Lab Sample#9 PH6121018-1 828 <br /> Linear€ Check: <br /> BTEX Benzene 0.9995 TPH Gasoline 0.9997 <br /> Toluene 0.9997 TPH Diesel N/A <br /> ' Ethyl Benzene M9999 Motor Oil N/A <br /> Xylenes M9999 TRPH (418.1) N/A <br /> ' MTBE D.9996 <br /> Std % Re ata biIi MTBE Benzene Toluene Eth Benz Xylenes <br /> ' BTEX 95 97 97 97 SS <br /> TPH Gasoline 91 TPH Diesel NIA <br /> TRPH (418.1) N/A TPH Motor Oil NIA <br /> ' Matrix S oike Recover€es MS MSD RPD <br /> MTBE 107.0 106.0 08 <br /> BTEX Benzene 901.0 900.0 1.0 <br /> Toluene 96.0 950 1.0 <br /> Ethyl Benzene 93.0 96.0 3.2 <br /> Xylenee 97.0 100.0 3.0 <br /> TPH Gasoline SPIKE INSIGNIFICANT RELATIVE TO SAMPLE CORN ERR <br /> ' TPH Diesel N/A N/A <br /> TRPH 418.1 NIA <br /> ' Method Blank MTBE Benzene Toluene Eth Benz Xylenes <br /> STEX <3 ug/L ¢.3 u L <.3 ug/L <.3 ug/L <.3 u L <br /> TPH Gasoline <50 u L TPH DlewI/MO <50 ug/L TRPH(418.1) N/A <br /> ' Lab Control Sample% Recovery EPA Performance Acceptance Range <br /> ' BTEX Benzene 98 37.0 - 131.0 <br /> Toluene 100 47.0 - 150.0 <br /> Ethyl Benz 99 36.9 - 162.0 <br /> ' Xylenes 101 42.7 - 137.9 <br /> TPH Gasoline 92 33.0 - 130.1 <br /> TPH Diesel N/A 45.1 - 135.2 <br /> ' TRPH (418.1) N/A NIA <br /> Gloria Poling, Lab Director <br />