Laserfiche WebLink
LABORATORY CONTROL SAMPLE EVALUATION REPORT <br /> GC Volatmles <br /> Client Lot #- . - : EOE180275 Work Order #. . . : DDK45102 Matrix. . . . . . . . . : WATER <br /> LCS Lot-Sample#: EOE230000-270 <br /> Prep Date. . . . . . : 05/22/00 Analysis Date. _ : 05/22/00 <br /> Prep Batch #. . . : 0144270 Analysis Time . : 09 23 <br /> ' Dilution Factor: 1 <br /> PERCENT RECOVERY <br /> ' PARAMETER RECOVERY LIMITS METHOD <br /> Benzene 106 (60 - 130) SW846 8021E <br /> Toluene 106 (60 - 130) SW846 8021B <br /> Ethylbenzene 103 (60 - 130) SW846 8021E <br /> ' Xylenes (total) 107 (60 - 130) SW846 8021E <br /> m-Xylene & p-Xylene 101 (60 - 130) SW846 8021B <br /> o-Xylene 106 (60 - 130) SW846 8021E <br /> PERCENT RECOVERY <br /> SURROGATE RECOVERY LIMITS <br /> ' a,a,a-Trifluorotolueaae 116 (60 - 130) <br /> (TFT) <br /> NOTE(S) : <br /> Calculations are performed before rounding to avoid round-off errors to calculated results <br /> Bold print denotes control parameters <br /> 1 <br /> ' <br /> 000027 <br />