Laserfiche WebLink
Pos"' STI SP-001 INSPECTION <br /> POWERS e°"" "� '° <br /> FF 707 9]6V GILLIESTRUCKIN3 $TOCKTON,CA <br /> FP%]0]B32 Y2Bi <br /> ENGINEERING&INSPECTION,INC. wwwY- Diesel Tank <br /> 1. Tank Inspection Summary <br /> 1.1. Tank Details <br /> General <br /> Tank Number: N/A <br /> Building Number: N/A <br /> Tank Type: AST Horizontal Cylindrical <br /> Design Standard: STI SP001 <br /> Construction date: arl I Unknown <br /> Manufacturer: Modesto Welding &Tanks <br /> STI SP001 Category: Category 1 <br /> Dimensions <br /> Diameter or Wdth: R. 8.00 <br /> Length: R. 27.00 <br /> Height: R. N/A <br /> Capacity: [gals] 10,000 <br /> Calculated Internal Capacity: gals] Unknown <br /> Vents <br /> Normal Vent: 2-in Open Vent <br /> Emer enc Vent: N/A <br /> Foundation/Containment <br /> Type: Concrete Slab <br /> Anchored? Yes <br /> Containment Volume: al -15,134 <br /> Covered Containment? No <br /> Continuous Release Detection Method CRDM ? Elevated AST <br /> Secondary Containment Type? Concrete Containment <br /> Grounding No <br /> Operational/Appurtenances <br /> Product Stored: Diesel <br /> Product Gravity: 0.88 <br /> Storage Temperature: Ambient <br /> Max Operating Pressure/Min Operating Pressure: Unknown <br /> Emergency Venting Capacity:[cfh[ Unknown <br /> Product Inflow/Outflow Rate: bbl./hr. Unknown <br /> Level Gauge Te: Electronic <br /> NFPA Placard: No <br /> Fuel Dis enser: /n Yes <br /> SIISPWI Ceres Tv Dlar Ta SbM ckZU Wba ° PnM 1 18 <br /> OMB£L lrc <br /> Page 8 <br />