Laserfiche WebLink
A <br /> t 110 2nd Avenue S"bwf#D7,Pacheco,CA 94553-5560 <br /> ell Analytical Inc. Telephone:;925-798-1620 Faii:925-798-1622 <br /> MCCarrlpb <br /> http://"V.mccampbell.com E-mail-main@mccampbelLcom <br /> r QC SUMMARY REPORT FOR SW8015C <br /> Matrix: SI I WorkOrder: 0308096 <br /> EPA Method: SW8015C Extraction: SW3550C Batch ID:8114 }J Spiked Sample ID: 0308096-005A <br /> Sample Spiked MS* MSD" MS-MSD LCS LCSD LCS-LCSD Acceptance Criteria(%) <br /> mg/Kg mg/Kg %Rec, %Rec. %RPD %[Rec. °/6 Rec. %RPD Low High <br /> TPH(d) ND 150 99.7 99 0.705 I10 110 0 70 130 <br /> %SS: 83.1 too 101 101 0 I 1 i h 110 0.822 70 130 <br /> I .t. - <br /> ;I. <br /> i All target compounds in the Method Blank of this extraction batch were ND less than the method RL with the following exceptions: <br /> • III <br /> _ NONE <br /> i <br /> ii <br /> mi <br /> i I) <br /> If <br /> I j�a <br /> i� <br /> !j <br /> 11 <br /> I <br /> �1 <br /> MS=Matrix Spike;MSD=Matrix Spike Duplicate;LCS=Laboratory Control Sample;LCSD=Laboratory Control Sample Duplicate;RPD=Relative Percent <br /> Deviation. h <br /> a {e <br /> /,Recovery=140'(M5-Sample)!(Amount Spiked);RPD=too•(MS-MSD)/(MS+MSD)"2. i <br /> MS and/or MSD spike recoveries may not be near 100%or the BPDs near 0%if:a)the sample is inhomogenous AND contains significant concentrations of <br /> analyte relative to the amount spiked,or b)if that specific sample matrix interferes with spike recovery.i <br /> N/A=not enough sample to perform matrix spike and matrix spike duplicate. .I! <br /> NR=analyte concentration in sample exceeds spike amount for soil matrix or exceeds 2x spike amouril for water matrix or sample diluted due to high matrix or <br /> analyte content. !, `r <br />