Laserfiche WebLink
Test Protocol (cont.) <br /> 9. Inspection of Lhe primary steel tank <br /> i. At this point the inspector should locate and note the leak detection port. <br /> v The integrity of the inner steel primary tank is accom nlished by checking for fluid between the stceltankandthe <br /> HDPE lines See below. <br /> Cross Section of ConVault <br /> no-uoid <br /> Interstice(betvmen <br /> nimary and Secondary) <br /> ron• „ <br /> Case:Steel tank is uncompgomised <br /> Result Fuel iernains safely stored in tank <br /> the inspectorshould obtain a clean Wood orplastic ospecoon(non-pointed)rod of sufficient lenyth in reach thefull depth <br /> of the lnnersteel tank. With the inspection porrcap opened,insert The rod to the bottom of the tube. <br /> iii. Withdraw the inspection rod and visually examine it. <br /> a. If the rod is dry and there is no liquid present then the primary steel tank is riot leaking and the ConVault <br /> is suitable for continued use <br /> See next page if the rod o wet. <br /> 888-965-3223 <br /> 4 c.n,n,.I m <br />