Laserfiche WebLink
Wk <br /> Spill Prevention, Control and Countermeasure Plan Y <br /> Tesla Treatment Facility Page 12 of 45 <br /> Table 2-1 Types of Oil and Containers <br /> Container Fluid Capacity Quantity Container Secondary <br /> (gallons) Material Containment <br /> Aboveground Bulk Diesel Fuel 8,000 gal 1 Steel Double-wall tank. Area <br /> Storage Tank No. 1 drains to retention pond. <br /> Aboveground Bulk Diesel Fuel 8,000 gal 1 Steel Double-wall tank. Area <br /> Storage Tank No.2 drains to retention pond. <br /> Aboveground Day Double-wall tank <br /> Tank in Standby integral and housed in <br /> Power Generator Diesel Fuel 150 gal 1 Steel power generator <br /> No. 1 enclosure. Area drains <br /> to retention pond. <br /> Single-wall container <br /> Engine Crankcase integral of transformer's <br /> in Standby Power Motor Oil 82 gal 1 Steel engine,sorbent and <br /> Generator No. 1 other spill containment <br /> supplies. Area drains to <br /> retention pond. <br /> Double-wall tank <br /> Aboveground Day integral and housed in <br /> Tank in Standby <br /> Power Generator Diesel Fuel 150 gal 1 Steel power generator <br /> No.2 enclosure. Area drains <br /> to retention pond. <br /> Single-wall container <br /> integral of transformer's <br /> engine,sorbent and <br /> Engine Crankcase other spill containment <br /> in Standby Power Motor Oil 82 gal 1 Steel supplies. Area drains to <br /> Generator No.2 retention pond.Area <br /> drains to retention pond. <br /> Area drains to retention <br /> pond. <br /> Single-wall tank integral <br /> and housed in <br /> Aboveground Tank Vegetable Oil-Based transformer enclosure, <br /> in Substation Dielectric Fluid 723 gal 1 Steel sorbent and other spill <br /> Transformer containment supplies. <br /> Area drains to retention <br /> pond. <br />