Laserfiche WebLink
10 E. FIELD INSTALLATION OF FIBERGLASS MONITOR PIPE <br /> * RELEASE VA,_UUM IN ANNULAR SPACE BY OPENING VACUUM GAGE MANIFOLD VALVE. <br /> * REMOVE EIV."IRE VACUUM GAGE MANIFOLD FROM THE TANK BY TWISTING AND <br /> PULLING THE MANIFOLD WITH YOUR HAND. THE MANIFOLD IS NOT THREADED <br /> INTO THE COUPLING, BUT IS SIMPLY SEATED WITH SILICONE SEAL. <br /> * CLEAN ALL SILICONE RESIDUE FROM THE INSIDE OF THE COUPLING BY SCRAPING <br /> AND SANDING. <br /> * INSTALL TEE 2" FIBERGLASS PIPE INTO THE COUPLING USING INSTRUCTIONS <br /> AND MATERIALS INCLUDED IN THE ADHESIVE KIT. <br /> * IF IT IS NECESSARY TO RE-APPLY VACUUM TO THE ANNULAR SPACE, PROCEED <br /> AS FOLLOWS; (SEE FIGURE 10E) : <br /> * I:NSTALL THE BELL x FEMALE ADAPTER COUPLING ON THE <br /> UPPER END OF THE 2" FIBERGLASS PIPE USING INSTRUCTIONS AND <br /> MATERIALS INCLUDED IN THE ADHESIVE KIT. <br /> * TEFLON TAPE AND INSTALL THE VACUUM GAGE MANIFOLD INTO <br /> THE COUPLING. <br /> * RE-APPLY VACUUM <br /> * ITEMS PROVIDED BY TRUSCO: <br /> (1) VACUUM GAGE MANIFOLD (ON TANK) <br /> (1) 2" FIBERGLASS PIPE x 5 ' LONG (TAPERED EACH END) <br /> (1) BELL x FEMALE ADAPTER COUPLING <br /> (1) ADHESIVE KIT <br /> (1) STRIP OF SAND PAPER <br /> VACUUM GAGE MANIFOLD <br /> (ONLY IF NECESSARY TO REAPPLY VACUUM) <br /> BELL x FEMALE THREAD n <br /> ADAPTER COUPLING (LCL <br /> (ONLY IF NECESSARY TO REAPPLY VACUUM) <br /> Z' FIBERGLASSBELL COMING <br /> PIPE x 5' LONG -_ (INSTALLED IN TANK) <br /> (TAPERED EACH END) <br /> MONITOR WELL <br /> TANK <br /> FIBERGLASS MONITOR PIPE INSTALLATION <br /> FIGURE 10E <br /> 11. FINAL NOTES: <br /> * IF ANY DAMAGE OCCUR TO THE SUPERTANK i" DURING INSTALLATION CONTACT A <br /> TRUSCO REPRESENTATIVE IMMEDIATELY. <br /> * THE PRIMARY TANK MUST BE REGULARLY INSPECTED FOR CONTAMINANTS. <br /> * CONTACT A TRUSCO REPRESENTATIVE FOR INFORMATION ON COMPATIBLE <br /> MONITORING SYSTEMS . <br /> * THE SUMP AREA MUST BE KEPT FREE OF FUELS AND WATER. <br /> rev. 8/31/90 <br /> 3 <br />