Laserfiche WebLink
M <br /> MAR 0 3 2004 <br /> SWRCB, January 2002 ENVIRONMENT HEAL] <br /> i <br /> PERMIT/SERVICES Ug. 7 of 7 <br /> QUICK N' SAVE/SOHOL MARKET <br /> 1901 S. El Dorado Street <br /> I Stockton, CA 95206 <br /> December 11 , 2003 <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not E uip ed With SpilUOverfill Containment Boxes <br /> 5 ilUOvert"ill Containment Boxes are Present, but were Not Tested [ 1 <br /> Test Method evelope. By: [ . ] Spill Bucket Manufacturer <br /> Other az [X ] Industry Standazd [ ] Professional Engineer <br /> Tes[ Method Used: [ ] Pressure [ ] Vacuum <br /> LAKE TEST Other SecLAKE TEST CX] Hydrostatic <br /> Test Equipment Used: Hydrostatic <br /> Equipment Resolution: <br /> S ill Box #1 Regular Sill Box #2 Su er Sill Box # Sill Box # <br /> pBucket <br /> iameter. 12" 12" <br /> e the 14" ] 4" <br /> e between <br /> 1MIN. 1 MIN. <br /> vacuum/water and <br /> est: <br /> Test Start Time: 9:30 AM 9:30 AM <br /> Initial Readin (Rl): 9" 8.5" <br /> Test End Time: 10:30 AM 10:30 AM <br /> Final Rea in Rt): 9" 8.5" <br /> Test Duration: 60 MIN. 60 MIN. <br /> Chan a in Readin (Rf RI -0- _0_ <br /> Pass/Fail Threshold or -0- <br /> .0. <br /> Criteria: <br /> j Test Result: fXI Pass Fail X Fass Fail Pass- Fail Pass Fail <br /> Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> RESEALED BOTTOM OF DRAIN BUCKETS <br />