F4Site Preparation and Installation Instructions <br />EIS -350 UST Monitoring System <br />SECTION 5. INTERSTITIAL LIQUID SENSOR <br />INSTALLATION <br />A. EQUIPMENT PREPARATION. <br />WWARNING: TO AVOID ELECTRICAL SHOCK WHICH <br />COULD KILL YOU, BE SURE AC POWER TO THE <br />MONITOR IS OFF DURING INSTALLATIOM <br />1. Turn OFF power to the ILS -350 system. <br />,j NOTE: Do not install the sensor if any liquid is present <br />in the annular space. Failure to comply will lead to an <br />alarm. <br />2. Make sure no liquid is present in the annular space. <br />B. INSTALLATION OF FLOAT SWITCH — <br />STEEL TANKS. <br />1. To be sure the sensor will reach the bottom of the annular <br />space, first measure the sensor riser pipe from the bottom <br />of the pipe to the top. Then measure the same distance up <br />the leader cable from its connection to the sensing element <br />and mark the leader cable. <br />16 CAUTION: DO NOT USE A KNIFE OR OTHER SHARP <br />OBJECT TO MARK THE LEADER CABLE. MARK THE <br />DISTANCE WITH A MARKER, TAPE, ORA TWIST TIE. <br />2. Lower the float switch assembly into the riser pipe until <br />the float switch touches the bottom of the tank (see Figure <br />12 "Float Switch Installation _ Steel Tanks"). <br />3. Keeping the cable taut, secure the sensor assembly in <br />place by attaching the cord grip. <br />NOTE: The float switch assembly must not hang by the <br />cable, but should rest slightly on the bottom of the tank <br />T supported by the cable. <br />4. Secure the riser cap to the riser pipe. <br />5. Tighten the cable bushing nuts on the riser cap and junc- <br />tion box to ensure a water -tight seal at the cable entry. <br />6. Using wire nuts, connect the two -wire sensor cable to the <br />field wires in the sensor junction box (see Figure 13 "Two - <br />Wire Sensor Field Wiring Diagram"). Since these are <br />contact switches, polarity is not a consideration when <br />connecting sensor wires to field wires. <br />,I NOTE: SEAL WIRE NUT CONNECTIONS AT THIS <br />qTIME USING epoxy sealant, furnished with each <br />sensor. <br />WARNING: EPDXY SEALANT MAY BE IRRITAT- <br />ING TO EYES AND SKIN. MAY CAUSE SKIN <br />SENSITIZATION IN SUSCEPTIBLE INDIVII)U- <br />ALS. MAY BE ABSORBED THROUGH THE SKIN. <br />EPDXY SEALANT CONTAINS EPDXY RESIN <br />AND VINYL CYCLOHEXENE DIOXIDE. VINYL <br />CYCLOHEXENE DIOXIDE HAS CAUSED SKIN <br />CANCER IN ANIMAL TESTS. <br />PRECAUTIONS: AVOID EYE AND SKIN CON- <br />TACT. WEARIMPERVIOUS GLOVES AND SAFE- <br />TY GLASSES. USE ONLY IN WELL VENTILATED <br />AREAS. <br />12 <br />Figure 12. Float Switch Installation — Steel'iAnks. <br />i <br />r <br />WEATHERPROOF <br />JUNCTION BOX <br />(1 PER PROBE) <br />1/2" RIGID <br />CONDUIT y BIk <br />TO <br />To SENSOR <br />!MONITOR <br />• <br />+ vr,c <br />Figure 13. Two -Wire Sensor Field Wiring Diagram. <br />M <br />M <br />