Laserfiche WebLink
9 . . <br />SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑Spill Bucket Manutacturrr ® Industry Stan chid ❑ Professional En inccr <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: 1 Hour Observed Test <br />Equipment Resolution: 1/16 of an inch <br />Spill Box # 91 Fill Spill Box # 91 Vapor Spill Box # Red Diesel Spill Box tr <br />Bucket Diameter: <br />12 inches <br />12 inches <br />12 inches <br />Bucket Depth: <br />15 inches <br />15 inches <br />15 inches <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 Minutes <br />10 Minutes <br />10 Minutes <br />Test Start Time: <br />14:30 <br />14:30 <br />14:30 <br />Initial Reading (Rt): <br />Top of Cap <br />Top of Cap <br />Top of Cap <br />Test End Time: <br />15:00 <br />15:00 <br />15:00 <br />Final Reading (RF): <br />Top of Cap <br />Top of Cap <br />Top of Cap <br />Test Duration: <br />1 hour <br />1 hour <br />1 hour <br />Change in Reading (RF -R,): <br />0 change <br />0 change <br />0 change <br />Pass/Fail Threshold or <br />Criteria: <br />1/16`h" <br />1/1 6th" <br />1/1 6th" <br />Test Result: <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />❑ Pass ❑ Dail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />