Laserfiche WebLink
Received on 10/23/2019 <br /> SJC EHD - CR <br /> Observations Comments/Recommendati ons <br /> econdar Containment T e waste Dike Wall <br /> scondary Containment Length 89" <br /> econdary Containment Wdth 17T' <br /> econdary Containment Height 8" <br /> econdary Containment Volume(gallons) 13488 <br /> econdary Containment Condition oreign Material Mustbe keptclean at all times. <br /> breaches,foreign material,liquid) <br /> econdary Containment Drain Valve es <br /> Installed? <br /> Drain Valve Looked? es <br /> um Pum Installed? A <br /> Is The Sump Pump Float Automatically or A <br /> anuafl Activated? <br /> Cher <br /> 3.0 Secondary Containment(AS7) <br /> Obs.rvations Comments/Recommendations <br /> econdary Containment(AST)- DAN,Double <br /> oft m or Secondary Containment(Pans, A <br /> oxes or Containers <br /> ST Containment Condition?Dry? A <br /> rain Valve Installed A <br /> rain Valve Looked? 10 <br /> ther <br /> 14.0 Tank Appurtenances <br /> ncillary Equipment-Piping/Piping ood <br /> onnections leaks,corrosion, su orts <br /> iDther <br /> Install anti-siphon valves where the liquid level in a tank <br /> nti Siphon Valve installed? 10 is at a higher elevation than the supply piping or <br /> dispensing unit. <br /> nti Siphon Valve Manufacturer /A <br /> nti Siphon Valve Model /A <br /> Is the Anti Siphon Valve Operational And A <br /> �roperly Sized? <br /> ire Valve Installed? A Product is feed from the top of the tank. <br /> ire Valve Manufacturer A <br /> ire Valve Model Number A <br /> ks the Fire Valve Operational? /A <br /> Me <br /> Vents Observations Comments/Recnmmendations <br /> ormal Vent Manufacturer DPW <br /> ormal Vent Size <br /> omral Vent Model 23 <br /> ormal Vent Condition Good <br /> Per NFPA 30 2015 21.4.3.3 Normal vents shall be sized <br /> n accordance with either API Standard 2000,Venting <br /> hnospheric and Low-Pressure Storage Tanks,or <br /> ormal Vent Properly Sized? Yes another approved standard.Altematively,the normal vent <br /> shall be at least as large as the largest filling or <br /> 'Mdrawal connection,but in no case shall it be less <br /> an 1?in. 3.2 an nominal inside diameter. <br /> 4 <br />