Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br />Tanknology Line Leak Detector Test <br />Work Order: 2330371 Date: 12/19/2016 <br />Site Name / ID: 7-ELEVEN #19976, MKT 2368 / 19976 <br />Address: 1399 N. MAIN ST. @ NORTHGATE <br />City: MANTECA State: CA Zip: 95336 <br />Tank ID <br />T4:UNLEADED <br />T5:PREMIUM <br />Product <br />RUL <br />PUL <br />Product Line <br />1 <br />1 <br />Tested From <br />1 <br />1 <br />Existing/New <br />Existing <br />Existing <br />FEB 0 2 <br />Mechanical/Electronic <br />Mechanical <br />Mechanical <br />Manufacturer/Model <br />Vaporless LD-2000 <br />Vaporless LD-200C <br />FNVIRON AENTAL H El <br />Serial No. <br />16101299 <br />16101298 <br />DEPARTMENT <br />Pump Operating Pressure (psi) <br />32.00 <br />32.00 <br />Calibrated Leak (mllmin) <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />Holding PSI <br />NIA for Electronic LD's <br />33.00 <br />32.00 <br />Resiliency (ml) <br />NIA for Electronic Lo's <br />130.00 <br />120.00 <br />Metering PSI <br />NIA for Electronic Lo's <br />20 <br />21 <br />Opening Time (sec) <br />N/A for Electronic Lo's <br />5 <br />3 <br />est Results <br />Pass <br />Pass <br />Technician Comments: Both leak detectors were tested from fueling point #1. <br />Technician Name: Darren Sciume Certification #: 103637 <br />Technician Signature: Expire Date: 10/2/2019 <br />Environmental Compliance for Petroleum Systems <br />© 2017 Tanknology Inc., Austin, Tx. All rights reserved. tanknology.com <br />X <br />[LTH <br />