Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2337558 Date: 9/17/2018 <br /> Site Name/ID: 7-ELEVEN#19976, MKT 2368/19976 <br /> Address: 1399 N. MAIN ST.@ NORTHGATE <br /> City: MANTECA State: CA Zip: 95336 <br /> Tank ID T4:UNLEADED T5:PREMIUM T4:UNLEADED <br /> Product RUL PUL RUL <br /> Product Line 1 1 1 <br /> Tested From 3 3 3 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-200C Vaporless LD-2000 Vaporless LD-200 <br /> Serial No. 16101299 16101298 16101299 <br /> Pump Operating Pressure(psi) 33.00 30.00 30.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 33.00 30.00 33.00 <br /> N/A for Electronic Lo's <br /> Resiliency(ml) 70.00 80.00 80.00 <br /> N/A for Electronic LD's <br /> Metering PSI 20 20 <br /> N/A for Electronic Lo's <br /> Opening Time(sec) 5 6 <br /> N/A for Electronic Lo's <br /> Test Results Fail Pass Pass <br /> Technician Comments:reg l.d. failed initial testing, was ajusted and passed <br /> Technician Name: Jarrod Cooke Certification#: 2081 <br /> Technician Signature: Expire Date: 2/24/2019 <br /> Environmental Compliance for Petroleum Systems <br /> ©2018 Tanknology Inc.,Austin,Tx. All rights reserved. tanknology.wm <br />