Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br />Tanknology Line Leak Detector Test <br />Work Order: 2332344 Date: 9/19/2017 <br />Site Name / ID: 7 -ELEVEN #19976, MKT 2368 / 19976 <br />Address: 1399 N. MAIN ST. @ NORTHGATE <br />City: MANTECA State: CA Zip: 95336 <br />Tank ID <br />T4:UNLEADED <br />T5:PREMIUM <br />Product <br />RUL <br />PUL <br />Product Line <br />1 <br />1 <br />Tested From <br />1 <br />1 <br />Existing/New <br />Existing <br />Existing <br />Mechanical/Electronic <br />Mechanical <br />Mechanical <br />Manufacturer/Model <br />Vaporless LD -2000 <br />Vaporless LD -200 <br />Serial No. <br />16101299 <br />16101298 <br />Pump Operating Pressure (psi) <br />35.00 <br />32.00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />Holding PSI <br />N/A for Electronic LD's <br />34.00 <br />32.00 <br />Resiliency (ml) <br />N/A for Electronic Lo's <br />100.00 <br />100.00 <br />Metering PSI <br />NIA for Electronic LD's <br />24 <br />21 <br />Opening Time (sec) <br />N/A for Electronic LD's <br />10 <br />2 <br />Test Results <br />Pass <br />Pass <br />Technician Comments: <br />Technician Name: Jesus Spaldivar Certification #: 115237 <br />Technician Signature: 4- ,� Expire Date: 12/27/2018 <br />Environmental Compliance for Petroleum Systems <br />0 2017 Tankndogy Inc., Austin, TX. All rights reserved. tanknology.com <br />