LDT 5000 Field Test Apparatus Page 1 of 1 <br />_,wTanknologyLine Leak Detector Test <br />Work Order: <br />Site Name / ID <br />Address: <br />City: <br />2306666 <br />Date: 10/29/2012 <br />7 -ELEVEN #19976, MKT 2368 / 19976 <br />1399 N. MAIN ST. @ NORTHGATE <br />MANTECA State: CA Zip: 95336 <br />Tank ID <br />T4 <br />T5 <br />Product <br />REG UNLEAD <br />PUL <br />Product Line <br />1 <br />1 <br />Tested From <br />1 <br />1 <br />Existing/New <br />Existing <br />Existing <br />Mechanical/Electronic <br />Mechanical <br />Mechanical <br />Manufacturer/Model <br />Vaporless LD -2000 <br />Vaporless LD -2000 <br />Serial No. <br />09070785 <br />unreadable <br />Pump Operating Pressure (psi) <br />28.00 <br />25.00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3 00 <br />3 00 <br />Holding PSI <br />NIA for Electronic Lo's <br />28.00 <br />25.00 <br />Resiliency (ml) <br />NIA for Electronic LD's <br />140.00 <br />160.00 <br />Metering PSI <br />N/A for Electronic LD's <br />15 <br />10 <br />Opening Time (sec) <br />N/A for Electronic Lo's <br />19 <br />42 <br />est Results <br />Pass <br />Pass <br />Technician Comments: <br />Technician Name <br />Technician Signature <br />Jarrod Cooke <br />Environmental Compliance for Petroleum Systems <br />© 2010 Tanknology Inc., Austin. TX. All nghts reserved. tanknology.com <br />Certification #: 1352 <br />Expire Date: 2/14/2013 <br />